Communication and system time startup fault scenarios
Secondary C300 Controller with Memory Retention
248 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Controller Faceplate Problem
C300 Block
Time Source
Station Alarm Resolve
Display
BKUP
CB icon
Yellow
Secondary C300 Controller with Memory Retention
Controller Faceplate Problem
C300 Block
Time Source
Station Alarm Resolve
Status
LED
Blinking
Red
FTE
LEDs
Off
Display
COMM
CB icon
Red
No communication on FTE
network.
None None Note 1
Status
LED
Blinking
Red
FTE
LEDs
Blinking
Green
Display
TS ->
IDLE
CB icon
Grey
Communication on FTE
network.
• No communication via CDA
• Unable to establish
connection to system time
source
None None Note 2
Status
LED
Blinking
Orange
FTE
LEDs
Blinking
Green
Display
BKUP
CB icon
Red ->
Blue
Communication on FTE
network
• Communication via CDA
• Unable to establish
connection to system time
source
CDA C300 Not
Synchronized
Note 3
Status
LED
Blinking
Orange
Communication on FTE
network
SNTP
• CDA comm
Lost
Note 4