Communication and system time startup fault scenarios
Non-redundant C300 Controller with Memory Retention
242 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Controller Faceplate Problem
C300 Block
Time Source
Station Alarm Resolve
CB icon
Grey
Status
LED
Blinking
Green
FTE
LEDs
Blinking
Green
Display
NODB
CB icon
Yellow
None. Normal operation for
non-redundant controller with
no battery backup following a
power cycle.
SNTP C300 Not
Synchronized
None.
Non-redundant C300 Controller with Memory Retention
Controller Faceplate Problem
C300 Block
Time Source
Station Alarm Resolve
Status
LED
Blinking
Red ->
Green
FTE
LEDs
Off
Display
BP for 2
min. TS
for 3 min.
then IDLE
CB icon
Red
No communication on FTE
network.
Internal C300 OFFNET Note 1
Status
LED
Blinking
Red ->
Green
FTE
LEDs
Blinking
Green
Display
TS for 3
min. then
-> IDLE
CB icon
Grey
Communication on FTE
network.
• No communication via CDA
• Unable to establish
connection to system time
source
Internal CDA Comm Lost
Connection
Note 2