Activate C300 Controller’s CEE
Initial activation order guidelines
172 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Icon Represents . . .
C300 Controller
(C300STATE)
(yellow & yellow)
Secondary C300 is not synchronized and
partner C300 is visible partner present.
Backup Soft Fail
(shadow &
yellow)
Secondary C300 is not synchronized and
partner C300 is absent or incompatible
Backup Soft Fail
Activate C300 Controller’s CEE
For the controller to begin executing its control strategy, you must activate the CEEC300
block.
Initial activation order guidelines
Make the initial activation of control strategy components in Control Builder from the
Monitoring tab in the following suggested order to minimize possible bad data generated
alarms.
Order Component
1 Control environment components such as:
CEEC300
ACE/CEE
2 Process Manager IOMs
3 PMIO I/O Channels
4 Fieldbus contained function blocks
5 Fieldbus device resident blocks
6 Input/Output Modules (IOMs)
7 Control Modules (CMs) and/or Sequential Control Modules (SCMs)
Activating the CEE
Follow the steps in the table below to activate the CEEC300 block.
Step Action
1
From the Monitoring Tree, right-click the CEE.