Communication and system time startup fault scenarios
Secondary C300 Controller with no Memory Retention
246 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Controller Faceplate Problem
C300 Block
Time Source
Station Alarm Resolve
Status
LED
Blinking
Red ->
Green
FTE
LEDs
Blinking
Green
Display
TS for 1
min.
then ->
IDLE
CB icon
Red
Communication on FTE
network
• Communication via CDA
• Unable to establish
connection to system time
source
CDA Not Using
Configured
Timesource
Note 3
Status
LED
Blinking
Orange ->
Orange
FTE
LEDs
Blinking
Green
Display
IDLE
CB icon
Grey
Communication on FTE
network
• No communication via CDA
• Established connection to
system time source
Controller transitions to
secondary redundancy role
assuming its partner has CDA
available.
SNTP CDA Comm Lost
Connection
Note 4
Status
LED
Green
FTE
LEDs
Blinking
Green
Display
IDLE
CB icon
Blue
None. Normal operation for
redundant controller with
battery backup following a
power cycle.
SNTP None None.
Secondary C300 Controller with no Memory Retention
Controller Faceplate Problem
C300 Block
Time Source
Station Alarm Resolve
Status
LED
Blinking
Red
No communication on FTE
network.
None None Note 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion C300 and is the answer not in the manual?

Honeywell Experion C300 Specifications

General IconGeneral
BrandHoneywell
ModelExperion C300
CategoryController
LanguageEnglish

Related product manuals