Fixing common problems
Duplicate Device Index setting
R301.1 Experion C300 Controller User's Guide 227
11/06 Honeywell
If Secondary C300 Controller synchronizes after replacement, the
removed C300 Controller is defective. Otherwise, go to Cause 2.
Cause 2
The Secondary IOTA is defective.
Solution
Replace the Secondary IOTA that initiated switchover when fault was
detected. See C300 Controller module and IOTA replacement for details.
If Secondary C300 Controller synchronizes after replacement, the
removed IOTA is defective. Otherwise, go to Cause 3.
Cause 3
The Primary C300 Controller is defective
Solution
Replace the Primary C300 Controller. See C300 Controller module and
IOTA replacement for details.
If you can command synchronization after replacement, the removed
C300 Controller is defective. Otherwise, go to Cause 4.
Cause 4
The primary IOTA is defective.
Solution
Replace the primary IOTA. See C300 Controller module and IOTA
replacement for details.
If the C300 Controller pair synchronize after IOTA replacement, The
removed IOTA is defective. Other wise, go to Cause 5.
Cause 5
There is a software problem.
Solution
Contact our Solution Support Center (SSC).
Duplicate Device Index setting
The FTE subsystem detects duplicate Device Index settings in separate nodes.
Diagnostic Check
All nodes will stop tracking cable status for the detected duplicate Device
Index value. Communications will continue and will not impact system
performance until there is a cable fault. This fault will also be detected by
the FTE System Management Tool.
A duplicate Device Index could cause a duplicate IP Address. In most
cases, the duplicate IP Address would be detected first and prevent the
FTE diagnostic messages from being sent.
Cause 1
Have set Device Index switches on separate IOTA's to same value.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion C300 and is the answer not in the manual?

Honeywell Experion C300 Specifications

General IconGeneral
BrandHoneywell
ModelExperion C300
CategoryController
LanguageEnglish

Related product manuals