IOLINK Block
Memory Stats tab
124 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Plain Text Parameter Name
User
Configurable
Notes
Partner I/F Not
Visible On IOL
PARTNOTVIS
No
Shows the Primary
IOLINK is unable to
view it's redundant
partner across the I/O
Link
Partner I/F Mismatch
On IOL
PARTMISMATCH
No
Shows the Primary
IOLINK is unable to
view it's redundant
partner across the I/O
Link
IOL Process Data
Cycle Overruns
IOLOVRRUN
No
Indicates whether or not
PV scanning from the
IOM or IOMs completed
within the IOM scan
rate timeframe.
UM51 Diagnositc
Exceeded Time
Threshold
UM51DIAGTMO
No
Indicates that one of the
online diagnostics has
exceeded its allotted
time period.
UM51 Diagnostic
Overrun
UM51DIAGFAILEDCO
MP
No
Indicates that one of the
online diagnostics did
not complete within its
time cycle.
Memory Stats tab
The Memory Stats tab contains data on the Non-Volatile Storage Memory usage for the
IOLINK interface. It also buttons to initiate commands for NVS compaction. The
following table summarizes the parameter data you can monitor and/or configure on the
Memory Stats tab of the configuration form for the selected IOLINK block.
Plain Text Parameter Name
User
Configurable
Notes
Memory Stats

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion C300 and is the answer not in the manual?

Honeywell Experion C300 Specifications

General IconGeneral
Controller TypeProcess Controller
Communication ProtocolsFoundation Fieldbus, HART
Power Supply24V DC
RedundancyOptional
Mounting OptionsDIN Rail
CertificationsFM

Related product manuals