EasyManua.ls Logo

Honeywell Experion C300 - Inhibit Sync Reason - RDNINHIBITSYNC

Honeywell Experion C300
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Redundancy parameters
Inhibit Sync Reason – RDNINHIBITSYNC
R301.1 Experion C300 Controller User's Guide 195
11/06 Honeywell
Reconnection of the redundancy cable.
Secondary module recovery from dual-FTE-cable disconnect
Secondary module powerup
Secondary module reboot into Backup state following firmware update.
Secondary module reboot into Backup state following recovery from the Fail state.
Auto synchronization retries
Once the Auto Sync State is enabled, loss of synchronization is automatically followed
by an automatic attempt to re-synchronize the redundant controller pair. However, after
a maximum of 3 initial-sync failures, the Auto Sync State is disabled with an inhibit sync
reason of Initial Sync Fail.
Inhibit Sync Reason – RDNINHIBITSYNC
Whenever the C300 is not in the synchronized/standby states and initial-sync is not in
progress, the RDNINHIBITSYNC parameter is set to the inhibit sync reason. Reasons
for inhibiting initial-sync include the following:
Inhibit Sync Reason Description
Startup In Progress Initial sync is not allowed until after the C300 has completed system
startup. This is a transient inhibit sync reason that is usually not
seen.
Auto Sync State Initial sync is inhibited while the Auto Sync State is set to disabled.
This is a persistent inhibit sync reason that is canceled via the
Enable Sync command.
Dropping Sync Initial-sync cannot commence until the previous abort sync
operation has been completed. This is a transient inhibit sync
reason that is usually not seen.
Initial Sync Delay There is a guaranteed 20 second delay in between initial-sync
attempts. More specifically, for 20 seconds after a compatible
partner is identified, initial-sync is inhibited with this transient
reason.
Initial Sync Fail After 3 failed attempts to perform initial-sync, the Auto Sync State is
automatically set to disabled and the inhibit sync reason is set to
this persistent value. Refer to the redundancy history for the
reasons why initial-sync failed, and issue the Enable Sync
command to attempt initial-sync again.
Redundancy
Configuration State
Initial-sync is not allowed when explicitly configured as non-
redundant. This persistent inhibit sync reason can only be canceled

Table of Contents