Convert a redundant C300 Controller to a non-redundant controller
To convert a redundant C300 Controller to a non-redundant controller
R301.1 Experion C300 Controller User's Guide 51
11/06 Honeywell
Step Action Result
7
Perform the procedure To configure a
Secondary C300 Controller block.
8
Select the Secondary C300 Controller
icon. Perform a Load to the controller.
The double ‘V’ sign next to the
Secondary C300 icon disappears in the
Project view.
9
Verify the redundant controller pair
achieves a synchronized state.
Convert a redundant C300 Controller to a non-redundant
controller
Prerequisites
• Control Builder is running
• Tree windows are open
• Make sure that the current primary C300 Controller is physically configured with the
odd Device Index. If not, enable synchronization, wait for initial-sync to complete,
and manually command switchover.
• The Primary C300 block must have RDNAUTOSYNC parameter set to disabled. If
not, issue the Disable Synchronization command (to either the primary or secondary
controller). A ‘Not Synchronized’ diagnostic alarm will be generated by both the
primary & secondary controllers
Considerations
This procedure can be performed on-process. All illustrations used in the procedure are
for example purposes only.
To convert a redundant C300 Controller to a non-redundant controller
Step Action Result
1
Disconnect the redundancy cable from
the primary C300 Controller.
Alarms are generated.
2
Remove the secondary controller
hardware by removing the controller
module and its IOTA.
Controller is removed from system.