Convert a redundant C300 Controller to a non-redundant controller
To convert a redundant C300 Controller to a non-redundant controller
R301.1 Experion C300 Controller User's Guide 51
11/06 Honeywell
Step Action Result
7
Perform the procedure To configure a
Secondary C300 Controller block.
8
Select the Secondary C300 Controller
icon. Perform a Load to the controller.
The double ‘V’ sign next to the
Secondary C300 icon disappears in the
Project view.
9
Verify the redundant controller pair
achieves a synchronized state.
Convert a redundant C300 Controller to a non-redundant
controller
Prerequisites
Control Builder is running
Tree windows are open
Make sure that the current primary C300 Controller is physically configured with the
odd Device Index. If not, enable synchronization, wait for initial-sync to complete,
and manually command switchover.
The Primary C300 block must have RDNAUTOSYNC parameter set to disabled. If
not, issue the Disable Synchronization command (to either the primary or secondary
controller). A ‘Not Synchronized’ diagnostic alarm will be generated by both the
primary & secondary controllers
Considerations
This procedure can be performed on-process. All illustrations used in the procedure are
for example purposes only.
To convert a redundant C300 Controller to a non-redundant controller
Step Action Result
1
Disconnect the redundancy cable from
the primary C300 Controller.
Alarms are generated.
2
Remove the secondary controller
hardware by removing the controller
module and its IOTA.
Controller is removed from system.