C300 Controller Block
QVCS tab
100 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Plain Text Parameter Name
User
Configurable
Notes
IOLink (1) Soft Fail
Error
IOL1SOFTFAIL
No
See IOLink 1 block Main
Tab.
IOLink (2) Soft Fail
Error
IOL2SOFTFAIL
No
See IOLink 2 block Main
Tab.
Debug Flag Enabled
DEBUGFLAGSET
No
Warning: Engineering
internal debug flag is set.
Minimum HW
Revision
MINHWREVSF
No
Partner Not Visible
On FTE
PARTNERNOTVISFTE
No
Indicates redundant
module partner is not
visible on FTE.
QVCS tab
The QVCS tab is common to all configuration forms for tagged blocks in Control
Builder. If you have a Qualification and Version Control System (QVCS) license, this tab
shows current QVCS information for the selected C300 block. Please refer to the online
help and the Qualification and Version Control System User’s Guide for more
information about the data on this tab.
Server History tab
The Server History tab is common to all configuration forms for tagged blocks in
Control Builder. The following table summarizes the parameter data you can monitor and
configure on this tab of the configuration form for the selected C300 block.
ATTENTION
The configuration settings you make for Server Load Options on the System
Preferences dialog determines whether or not the data entered on the
Server History tab is loaded to the Experion Server. See the Control Building
Guidefor information about setting system preferences.
Plain Text Parameter Name
User
Configurable
Notes
Access Levels
Control Level
SCANCTRLLVL
Yes
Indicates Server control