C300 Controller Block
Soft Failures tab
R301.1 Experion C300 Controller User's Guide 99
11/06 Honeywell
Plain Text Parameter Name
User
Configurable
Notes
Soft Failure Conditions
Battery State
Warning
BATTERYNOTOKSFTA
B
No
Indicates the status of
CPM battery. Status is
also shown on Main tab of
C300 block.
Device Index
Switches Changed
BCDSWSTS
No
Online diagnostic warning:
Switches broken or
deliberately changed.
Factory Data Error
FACTDATAERR
No
Online diagnostic error
reading factory data.
ROM Application
Image Checksum
Failure
ROMAPPIMGCHKSMF
AIL
No
Online diagnostic error:
ROM application image
CRC.
ROM Boot Image
Checksum Failure
ROMBOOTIMGCHKSM
FAIL
No
Online diagnostic error:
ROM boot image CRC
WDT Hardware Error
WDTHWFAIL
No
Online diagnostic error:
Hardware Watchdog
Timer is not responding.
WDT Refresh
Warning
WDTSWFAIL
No
Online diagnostic warning:
Watchdog Timer is being
refreshed unacceptably
close to the timout limit.
Critical Task
Watchdog Warning
TASKHLTHMON
No
Uncorrectable
Internal RAM Sweep
Error
RAMSWEEPERR
No
Uncorrectable single-bit
errors in Main RAM.
Corrected Internal
RAM Sweep Error
RAMSCRUBERRS
No
Corrected single-bit errors
in Main RAM.
Uncorrectable User
RAM Sweep Error
BACKUPRAMSWEEPE
RR
No
Uncorrectable single-bit
errors in Application RAM.
Corrected User RAM
Sweep Error
BACKUPRAMSCRUBE
RRS
No
Corrected single-bit errors
in Application RAM.