Disable Synchronization command
Prerequisites
178 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Disable Synchronization command
You can use the following procedure to disable synchronization manually to a redundant
C300 Controller pair.
Prerequisites
You can view active redundant C300 Controller pair on the Monitoring tab in
Control Builder.
The primary and secondary C300 Controllers are synchronizing, synchronized or in
standby state.
To Disable Synchronization
Step Action
1
In the Monitoring tab, double-click the primary C300 icon to call up its
Parameters configuration form.
2
Click the Redundancy tab to display it.
3
Click the Disable Synchronization button.
4
Click the Yes button to confirm the action and issue the Disable
Synchronization command.
5
Confirm that the Auto Synchronization State becomes DISABLED.
6
Click the OK button to close the Parameters form.
7
This completes the procedure.
Initiating Become Primary command
You can use the following procedure to manually cause an unsynchronized secondary
controller to transision into a primary role in the absence of a partner controller.
Prerequisites
You can view active redundant C300 Controller pair on the Monitoring tab in
Control Builder.
The unsynchronized secondary controller has no view to a partner controller across
the redundancy cable and the primary IP address is currently not occupied.