EasyManuals Logo

Honeywell Experion C300 User Manual

Honeywell Experion C300
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
C300 Controller Block
Server History tab
R301.1 Experion C300 Controller User's Guide 101
11/06 Honeywell
Plain Text Parameter Name
User
Configurable
Notes
level to be associated with
this function.
History Configuration
Number of History
Parameters
HIST.NUMPARAMS
Yes
Defines number of history
parameters to be included
in History Configuration
table.
Parameter
HIST.PARAM
Yes
Valid parameter name for a
parameter associated with
the given point that is to be
collected and stored as
historical data at
predetermined intervals.
Description
No
Provides a brief description
of the entered parameter.
FAST
HIST.FAST
Yes
Select the Fast type of
history collection.
STD
HIST.STD
Yes
Select the Standard type of
history collection
EXTD
HIST.EXTD
Yes
Select the Extended type of
history collection
Gating Parameter
HIST.GATEPARAM
Yes
Optional gating parameter
to define conditions under
which data for this
parameter should be
collected.
Gate State
HIST.GATEVALUE
Yes
Defines gate state for
configured gating
parameter.
Create New or Edit
Existing Server
Scripts (Button)
N/A
Launches the Server
scripting configuration
utility.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Experion C300 and is the answer not in the manual?

Honeywell Experion C300 Specifications

General IconGeneral
BrandHoneywell
ModelExperion C300
CategoryController
LanguageEnglish

Related product manuals