EasyManua.ls Logo

LOYTEC L-Gate - Terminal Layout and Power Supply; Wiring

Default Icon
161 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L-Gate User Manual 22 LOYTEC
Version 3.2 LOYTEC electronics GmbH
DIP Switch # Function Factory Default
1 Must be OFF OFF
2 Must be OFF OFF
3 Must be ON ON
4 Must be OFF OFF
5 Must be OFF OFF
6 Must be OFF OFF
7 Must be OFF OFF
Table 3: DIP Switch Settings for L-Gate
3.7 Terminal Layout and Power Supply
The L-Gate provides screw terminals to connect to the network as well as to the power
supply. The screw terminals can be used for wires of a maximum thickness of 1.5
mm
2
/AWG12. The device can either be DC or AC powered.
Terminal Function
1 BACnet MS/TP Ground
2 BACnet MS/TP Non-Inverting Input
3 BACnet MS/TP Inverting Input
4 Earth Ground
5, 6 CEA-709 A, B of FT-10 Channel Port
8 Ethernet 100BaseT
15 Earth Ground
16, 17 Power Supply 12-35 VDC or 12-24 VAC ± 10%
Do not connect terminal 17 to earth ground!
Table 4: L-Gate Terminals LGATE-900.
3.8 Wiring
The CEA-709 network segment connected to the L-Gate needs to be terminated according
to the rules found in the specification of the transceiver (see Section 8.1). If BACnet is
configured to run over MS/TP, the MS/TP network segment must be properly terminated
with an LT-04 network terminator connected at each of the two ends of the segment media.
Important: When using shielded network cables, only one side of the cable should be connected to
earth ground. Thus, the shield must be connected to earth ground either at the L-Gate
terminals or somewhere else in the network.
Important: When using 2-wire MS/TP, earth ground must be connected to both terminal 15 and 16
(see Figure 9a). Never connect terminal 17 to earth ground!

Table of Contents