L-Gate User Manual 45 LOYTEC
Version 3.2 LOYTEC electronics GmbH
Figure 37: CEA-709 Statistics Page
4.3.6 BACnet MS/TP Statistics
The BACnet MS/TP statistics page is only available, when the BACnet port is configured
for the MS/TP data link layer (see Section 4.2.7). An example is shown in Figure 38. The
separated part on the top of the table contains the most important statistics data.
Figure 38: BACnet MS/TP Statistics Page
The MS/TP token status reports the current token passing state. In state OK, the token is
circulating between the masters. This is the normal state, when multiple masters are on the
MS/TP network. The state SOLE MASTER is the normal state when the device is the only