3. Wiring Method
3-6
3.2.3 Dimensions for Power Circuit Electrical Parts
Name
XDL-
L7SA001□
XDL-
L7SA002□
XDL-
L7SA004□
XDL-
L7SA008□
XDL-
L7SA010□
XDL-
L7SA020□
XDL-
L7SA035□
XDL-
L7SA050□
MCCB(NFB)
30A Frame 5A (ABE33b/5)
30A Frame
10A
(ABE33b/10)
30A Frame 15A (ABE33b/15) 30A Frame 30A (ABE33b/30)
50A Frame
40A(ABE53b
/40)
Noise Filter
(NF)
TB6-B010LBEI(10A) TB6-B030NBDC(30A)
TB6-
B040A(40A)
DC reactor
HFN-10 (10 A) HFN-15 (15 A) HFN-30 (30 A)
HFN-
40(40A)
MC
11A / 240V
(GM-9)
18A / 240V
(GM-18)
32A / 240V
(GM-32)
50A / 240V
(GM-50)
Wire
L1,L2,L3
PO,PI,N,
B+,B,BI
U,V,W
AWG16
(1.5 ㎟)
AWG14
(2.5 ㎟)
AWG12
(4.0 ㎟)
AWG10 (6.0
㎟)
C1
C2
AWG16(1.5 ㎟) AWG16(1.5 ㎟) AWG16(1.5 ㎟)
AWG16(1.5
㎟)
Crimp terminal
UA-F1510, SEOIL
(10 mm Strip & Twist)
UA-F2010, SEOIL
(10 mm Strip & Twist)
UA-F4010, SEOIL(10 mm
Strip & Twist)
GP110028
KET
Regenerative
resistance
(Provided by
default)
50 [W]
100
100 [W]
40
150 [W]
13
120[W]
6.8
Connector
(L1,L2...U,V,W
)
• BLF 5.08/03/180F SN BK BX
• BLF 5.08/11/180F SN BK BX
• BLZ7.62HP/03/180LR
SN BK BX SO
BLZ7.62HP/11/180LR
SN BK BX SO
Note1) Use 600V-PVC Insulated wire for wiring.
Use approved UL wire (Temp. 60℃ or above) for UL (CSA) Regulation.
Use approved wire for any other regulations.
Use equivalent or advanced components compare to components above for any special applications.