192 SyncServer 600 Series User’s Guide 098-00720-000 Revision D1 – February, 2018
Chapter 6 Provisioning
Provisioning Inputs with Manual Entry Controls
Table 6-10. Situations where use of manual time-information can allow for full capability on outputs
Input Time
Reference
Information
not provided
by this timing
reference
category
Impact to outputs
if not manually
supplied (or
provided by other
qualified input)
Remedy
Notes
Any IRIG
that includes
current year,
other than
1344 or
C37.118
No UTC
offset from
TAI
No pending
leap
PTP:
can't set TAI
timescale
can't set
UTCoffsetValid
flag
can't indicate
pending leap
NTP:
can't indicate
pending leap
IRIG1344/C37.118:
can't indicate
pending leap
Manually set:
utc offset
pending leap
IRIG is presumed
to always supply
UTC timescale.
IRIG "no
year"
No UTC
offset from
TAI
No Current
year
No pending
leap
PTP:
can't set TAI
timescale
can't set
UTCoffsetValid
flag
can't indicate
pending leap
NTP:
can't provide
UTC time
can't indicate
pending leap
IRIG1344/C37.118:
can't provide
UTC time
can't indicate
pending leap
Manually set:
utc offset
pending leap
current year
These IRIG codes
are a subset that do
not provide the
current year. For
standard coding of
IRIGs, the codes
that lack year have
last digit in the
range 0 - 3. If range
is 4 - 7 the year is
provided. For
example, B000 -
B003 do not
provide year, B004
- B007 provide
year.