Alarms: There are four standard alarms: transmitter output level (TX Fail), low received signal level
(Low Sig), communications channel failure (Logic Alarm), and power supply failure.
Alarm Relay Characteristics:
Maximum continuous current; 1 Amp
Maximum breaking current (125 Vdc): 1 Amp, non-inductive
Maximum breaking current (280 Vdc): 0.25 Amp, non-inductive
Maximum open circuit voltage; 280 Volts
Interface Dielectric Strength: All input and output circuits are isolated from ground and from all other
circuits. Breakdown is 1500 Vrms @ 50/60 Hz, 2500 Vdc, and 2500 Vrms @ 1.5 MHz, in
accordance with IEEE Surge Withstand Capability Specification 472-1978 (ANSI C.37.90-1978).
The RFL 9780 also meets the requirements of ANSI-IEEE Fast Transient Specification C.37.90.1-
1988.
Input Power Requirements:
Voltage Range:
48-Vdc Systems: 40 Vdc to 58 Vdc.
125-Vdc Systems: 103 Vdc to 155 Vdc.
250-Vdc Systems: 200 Vdc to 300 Vdc.
Power Consumption: 85 watts max.
Operating Temperature: -20
o
C to +60
o
C (-4
o
F to +140
o
F).
Dimensions:
Height: 10.5 inches (267 mm).
Depth: 13.0 inches (330 mm).
Overall Width: 19 inches (483 mm).
Weight: Less than 30 lbs (13.6 kg).