Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-11
I/O modules PCD3
Digital input modules
6
6.2 Digital input modules
PCD3.E110 8 inputs 8 ms, 24 VDC
PCD3.E111 8 inputs 0.2 ms, 24 VDC
PCD3.E112 8 inputs 9 ms, 12 VDC
PCD3.E116 8 inputs 0.2 ms, 5 VDC
PCD3.E160 16 inputs 8 ms,
connection via 34-pole ribbon connector
PCD3.E161 16 inputs 0.2 ms,
connection via 34-pole ribbon connector
PCD3.E165 16 inputs 8 ms,
connection via 24-pole spring terminal block
PCD3.E166 16 inputs 0.2 ms,
connection via 24-pole spring terminal block
Denition of input signals
for 5 VDC for 12 VDC for 24 VDC
PCD3.E116 PCD3.E112 PCD3.E110, PCD3.E111,
PCD3.E160 … E166
7 VDC
5 VDC
2.5 VDC
0 VDC
1 VDC
-7 VDC
1
0
15 VDC
12 VDC
7.5 VDC
0 VDC
2.5 VDC
-15 VDC
1
0
30 V
DC
24 V
DC
15 V
DC
0 V
DC
5 V
DC
-30 V
DC
1
0
I/O modules and I/O terminal blocks may only be plugged in and removed when the
Saia PCD
®
and the external +24V are disconnected from the power supply.