EasyManua.ls Logo

SBC PCD2 Series - PCD2.W525 Combined Analogue Input;Output Modules with Galvanic Isolation

SBC PCD2 Series
330 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-98
I/O modules PCD1|PCD2
PCD2.W525 Combined analogue input/output module with galvanic isolation
5
5.13.1 PCD2.W525 Combined analogue input/output modules
with galvanic isolation
General Information
PCD2.W525 is an analogue multipurpose module with four inputs and two outputs.
Eachinputandeachoutputcanbeindividuallyconguredasoneofthestand-
ardindustrialinterfacetypelike0 … 10V,0 … 20mAand4 … 20mA.Inaddition,
theinputscanbeconguredtosupportPt/Ni1000orPt500temperaturesensors.
Furthermore,themoduleo󰀨ershighexibilityinselectingltertypesandscaling
ranges.
Inputs-14 Bit
● 4Inputs.Everychannelhasfourmodesofoperation(congurablebyDIP-
Switches):
○ DierentialVoltageInputs
0 … 10V,resolution:0.61mVperLSB(14Bit)
○ DierentialCurrentInputs-measuredindi󰀨erentialmode
0 … 20mA,resolution:1.2μAperLSB(14Bit)
4 … 20mA,resolution:1.2μAperLSB(13.7Bit)
○ Temperature
Pt1000,-50 … 400°C,resolution:0.1°C
Pt500,-50 … 400°C,resolution:0.2°C
Ni1000,-60 … 200°C,resolution0.1°C
○ Resistance
0 … 2500Ω,resolution0.2Ω
● Eachchannelcanbeconguredtohaveasoftwarebased50Hz/60Hzlter
Outputs-12 Bit
● 2Outputs.Everychannelhasthreemodesofoperation(congurablebysoft-
ware):
○ Voltage
0 … 10V,resolution:2.44mVperLSB(12Bit)
○ Current
0 … 20mA,resolution:4.88μAperLSB(12Bit)
4 … 20mA,resolution4.88μAperLSB(11.7Bit)
○ Highimpedance
Miscellaneous
All I/O-Channels are galvanically isolated to the Saia PCD
®
and external power
supply. (But all channels are galvanically connected to each other.)
Every channel has two connection terminals.

Table of Contents