Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-48
I/O modules PCD3
PCD3.A860
6
6.6.2 PCD3.A860, digital light and shade module, with 2 make contacts
Application
The module is a light and shade module with a manual control option. The desired
functionalitycanbeselectedintheuserprogram.Therearetwoecientmake
contacts (without suppressors) and 2 digital inputs. It is also possible to operate
this module in "transparent mode". In this mode, the module is a pure I/O module
with two inputs/outputs.
Technical data
Digital inputs: 2
Digital outputs: 2
Contact type 2 make contact
Nominal voltage: 12 A / 250 VAC each
Peak start-up current (20 ms): 80 A (AC)
Reverse voltage protection (U
ext
): yes
Timeconstantofinputlter: typically 6 ms
Internal current consumption:
(from +5 V bus)
max. 40 mA
(both input LEDs on)
Internal current consumption:
(from V+ bus)
0 mA
External current consumption: max. 40 mA
(both relay coils live, both output LEDs on)
Terminals, Relay outputs:
Sensor inputs:
1 x pluggable 4-pole cage clamp terminal block
(4 405 5027 0), for wires up to 2.5 mm²,
or as above with 4 grouped strands, numbered,
2.5 m long (PCD3.K860)
1 x pluggable 6-pole cage clamp terminal block
(4 405 5028 0), for wires up to 1.0 mm²,
or as above with 6 grouped strands, numbered,
2.5 m long (PCD3.K861)