Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-8
I/O modules PCD3
Introduction to I/O modules
6
6.1.2 Current consumption of the modules
Type
PCD3…
Internal current
consumption
I from +5 V [mA]
Internal current
consumption
I from V+ [mA]
External current
consumption
I from 24 VDC
E11x 1…24 -- max. 48 mA
E16x 1…10 -- max. 64 mA
E500 1 -- --
E61x 1…24 -- max. 40/30 mA
A200 1…15 -- max. 32 mA
A210 1…15 max. 32 mA
A220 1…20 -- max. 48 mA
A251 1…25 -- max. 64 mA
A300 1…20 -- Load current
A400 1…25 -- Load current
A410 1…24 -- Load current
A46x max. 10 -- Load current
A810 40 -- --
A860 18 -- --
B100 1…25 -- Load current
B100 120 -- Load current
W200/210 8 5 --
W220 8 16 --
W300/310 8 5 --
W340/360 8 20 --
W350 8 30 --
W380 25 25 --
W3x5 60 -- --
W4x0 1 30 100 mA (W410)
W600 max. 4 20 --
W610 max. 110 -- max. 100 mA
W6x5 110/55 (W615) 90 (W615) max. 90 mA (W615)
W500 max. 200 -- --
W525 40 0 --
W7x0
W745 200 --
W800 45 35
H100 90 -- CCO output, load current
H110 90 -- Load current
H150 25 -- Load current
H210 ¹) 85 -- Load current
H31x ¹),
2
) 140 -- max. 15 mA
¹) These I/O modules cannot currently be used with the PCD3 RIO head station
2
) for H311: up to max. 300 mA for the encoder, this current also loads the +5V bus on the module