I/O modules PCD1|PCD2
PCD2.G410
5
5.7.2 PCD2.G410, multi-functional I/O module
with elect. isolated digital I/O
Application
Combined module with digital and analogue inputs and outputs. This module is
designed to extend the range of uses for the Saia PCD
®
. The functions and the
technicalspecicationarebasedontheexistingPCD2modules.
This module cannot be installed in the PCD1.
The technical details should be taken from the descriptions of these modules.
Number and type of inputs/outputs
16 digital inputs,electricallyisolated,E0 … E15,(addresses0 … 15).
Tech. data as for PCD2.E610,
Source or sink operation selectable via “Q/S” jumper.
4 relay outputs,A16 … A19(addresses16 … 19),
Each with a changeover contact protected with 2 varistors.
Tech. data as for PCD2.A200.
The 24 V supply to the relay coils is via the screwless terminals “U
ext
”, located
next to the 4 relays.
4 analogue outputs,with8bitresolution,A32 … A35
(baseaddress32*,channels0 … 3)
Eachchannelselectablewith“U/I”jumperforvoltage0 … 10V
orcurrent0 … 20 mA.
Tech. data as for PCD2.W410.
4 analogue inputs,with10bitresolution,E48 … E51
(baseaddress48*,channels0 … 3)
Eachchannelcanbeconguredseparatelywiththejumpercombinationsshown
forvoltage0 … 10V(“U”),current0 … 20mA(“I”)orforresistivetemperature
sensorsPt/Ni1000(“T”)foratemperaturerangefrom-20 … +100°C.
Tech. data as for PCD2.W2xx.
Internalcurrentconsumptionfrom +5Vbus 10 … 50mA
V+bus 10 … 40mA
24 V connection (U
ext
): This is located next to the 4 relays as screwless terminal
“U
ext
”.
The 24 V supply is common to the relay coils and the
external supply to the analogue outputs.
Current consumption: 9 mA per relay
20 mA per analogue output
*(whenthemoduleisinstalledonsockets1 … 4onthePCD2).