EasyManua.ls Logo

SBC PCD2 Series - PCD2.A400, 8 Digital Outputs for 0.5 a each

SBC PCD2 Series
330 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-26
I/O modules PCD1|PCD2
PCD2.A400
5
5.4.2 PCD2.A400, 8 digital outputs for 0.5 A each
Application
Lowcostoutputmodulewith8transistoroutputs5 … 500mA,withoutshortcircuit
protection.Fornon-isolatedcircuitsinthevoltagerange5 … 32VDC.
Technical data (forversion“B”)*
Number of outputs: 8, electrically connected
Output current: 5 … 500mA(leakagecurrentmax.0,1mA)
Withinthevoltagerange5 … 24VDC, the load re-
sistance should be at least 48 Ω
Total current per module: 4 A on 100 % duty cycle
Operating mode: Source operation (positive switching)
Voltage range: 5 … 32 VDC, smoothed
10 … 25VDC, pulsed
Voltage drop: ≤0.4Vat0.5A
Output delay: Switch-on delay typically 10 µs
Switch-o󰀨delaytypically50µs
(ohmicload5 … 500mA),longerwithinductiveload,
because of the protective diode.
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling
(whole trunk group)
Internal current consump-
tion: (from +5 V bus)
1 … 25mA;typically15mA
Internal current consump-
tion: (from V+ bus)
0 mA
External current consump-
tion:
Load current
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
* Version “B” available since February 1995
(Version“A”wasttedwithbipolartransistors.Thesehadashorterrecovery
time, but also a higher residual voltage, resulting in a restriction on 100 %
loading)

Table of Contents

Related product manuals