Protection parameter group 06
PARAMETER DESCRIPTION 115
5.7.8 Input phase loss protection
Turn on input phase failure protection
Parameter
Name
Default
Setting Range
Content
06-13
P.281
Input phase loss
protection
0
0
Off
1
When input phase loss, built-in keypad shows IPF alarm and
inverter stops
Input phase loss protection
When 06-13(P.281)=1, input phase loss protection is on; when input power is out of phase inverter will trigger
alarm IPF.
5.7.9 Time record function
It is used to record the inverter accumulative operation time.
Parameter
Name
Default
Setting Range
Content
06-27
P.292
Total inverter operation time
(minutes)
0 min
01439 min
---
06-28
P.293
Total inverter operation time
(days)
0 day
09999 day
---
06-29
P.296
Total inverter power on time
(minutes)
0 min
01439 min
---
06-30
P.297
Total inverter power on time
(days)
0 day
09999 day
---
Time record function
06-27(P.292)/06-29(P.296) is operation minutes of the inverter. The value cannot be changed when 00-02=3
(P.998=1) is executed or power is cut off, but can be cleared when set 06-27(P.292)/06-29(P.296) to 0.
06-28(P.293)/06-30(P.297) is operation days of the inverter. The value cannot be changed when 00-02=3
(P.998=1) is executed or power is cut off, but can be cleared when set 06-28(P.293)/06-30(P.297) to 0.
Setting
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SC3 Series and is the answer not in the manual?

Shihlin electric SC3 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSC3 Series
CategoryInverter
LanguageEnglish

Related product manuals