Digital input/ output parameter group 03
PARAMETER DESCRIPTION 95
5.4.4 Digital output signal delay
This parameter is used to delay and confirm the digital output signal. Delay time acts like confirmation time, which
can prevent some unknown interference.
Parameter
Name
Default
Setting Range
Content
03-16
P.120
Output signal delay
time
0.0s
03600.0s
---
Output signal delay
When set 03-16(P.120)=0 and condition from 03-11 (P.85) is met, signal will output directly.
When set 03-16(P.120)0.1~3600 and condition from 03-11 (P.85) is met, signal will output after delay time.
5.4.5 Digital input signal filter
This parameter is used to set response time for digital input signals.
Parameter
Name
Default
Setting Range
Content
03-17
P.157
Digital input terminal
filter time
4
02000
---
Digital input terminal filter
03-17 (P.157) is used to select the response time of the digital input terminal signal, the terminal includes: STR,
STF, M0, M1. The actual delay time is 03-17(P.157)*2ms, for example, when 03-17(P.157)=100, the actual delay
time is 200ms.
Setting
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SC3 Series and is the answer not in the manual?

Shihlin electric SC3 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSC3 Series
CategoryInverter
LanguageEnglish

Related product manuals