Basic operation steps for different modes
BASIC OPERATION 41
4.3.3 Basic operation steps for JOG mode (00-16(P.79)=0 or 1)
• Switch operation mode to JOG mode and indicator in will light up, the display shows .
Note: 1. For detailed operating procedures for the monitor mode, please refer to section 4.2 Operation modes of inverter.
• Press or to run the motor. At this point, indicator in will flicker, indicating that the motor is running.
• Release or to decelerate the motor until it comes to a full stop. Indicator in will not turn off until the
inverter stops the output.
Note: 1. For detailed operating procedures for monitor mode, please refer to section 4.2.3.
2. In JOG mode, target frequency is the value of 01-13(P.15) , and the acceleration / deceleration time is the value of
01-14(P.16). Please refer to section 5.2.7 JOG operation.
4.3.4 Basic operation steps for communication mode (00-16(P.79)=3)
In communication mode, user can set parameters and run/stop or reset inverters by communication. Please refer
to Communication function related parameters
for details.
4.3.5 Basic operation steps for combined mode 1 (00-16(P.79)=4)
•
In Combined Mode 1, indicator will light up.
Note: 1. For detailed operation procedures for monitor mode, please refer to section 4.2.
• Enter frequency setting mode and write target frequency into memory.
Note: For setting details, please refer to section 4.2.4.
• Set target frequency by built-in keypad and start the inverter by terminal STF/STR .
• At this point, indicator in
will flicker, indicating that the motor is running.
Note: For detailed operation procedures for monitor mode, please refer to section 4.2.3.
• When terminal STF/STR signals turn off, motor will decelerate until it comes to a full stop.
• Indicator in
will not turn off until the inverter stops outputting.