System parameter group 00
PARAMETER DESCRIPTION 50
5.1.2 Parameter restoration
Set parameters back to default.
Parameter
Name
Default
Setting Range
Content
00-02
Parameter
restoration
0
0
Off
1
Clear alarm history (P.996=1)
2
Reset inverter (P.997=1)
3
Restore all parameters to default (P.998=1)
4
Restore some parameters to default 1 (P.999=1)
5
Restore some parameters to default 2 (P.999=2)
6
Restore some parameters to default 3 (P.999=3)
Parameter restoration
1: When 00-02(P.996~P.999) is set to 1, screen will flash , the alarm record will be erased after writing,
and 00-02(P.996~P.999) is reset to 0.
2: When 00-02(P.996~P.999) is set to 1, screen will flash , and inverter will be reset, then
00-02(P.996~P.999) is reset to 0. After resetting the inverter, the accumulated values in electronic thermal relay
and IGBT module thermal relay will be set to zero.
3: When 00-02(P.996~P.999) is set to 3, screen will flash all the parameters will be restored to the
default values except the parameters in table 1 below. After parameters are restored, 00-02(P.996~P.999) is reset
to 0.
Exception
The parameters in table 1 below will not be restored to the default values:
Group
No.
Name
00-00
P.90
Inverter model
00-01
P.188
Firmware version
00-23
P.186
Motor types selection
00-24
P.189
50Hz/60Hz switch selection
00-25
P.990
Parameter display mode setting
01-08
P.21
Acceleration/deceleration time increments
06-27
P.292
Total inverter operation time (minutes)
06-28
P.293
Total inverter operation time (days)
06-29
P.296
Total inverter power on time (minutes)
06-30
P.297
Total inverter power on time (days)
4 : When 00-02(P.996~P.999) is set to 4, screen will flash all the parameters will be restored to the
default values except the parameters in table 1 and table 2 below after writing. After parameters are restored,
00-02(P.996~P.999) is reset to 0.
Exception
The parameters in table 2 below and table 1 will not be restored to default values:
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SC3 Series and is the answer not in the manual?

Shihlin electric SC3 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSC3 Series
CategoryInverter
LanguageEnglish

Related product manuals