Application parameter group 10
PARAMETER DESCRIPTION 147
5.10.5 Remote setting function selection
If operation box is located away from control cabinet, without analog signal, variable speed can still be realized
through digital input.
Remote control function, frequency save in memory
Remote control function, frequency won’t save
Remote control function, frequency won’t save, clear
frequency setting every time STF/STR “turn off”.
Remote control function, frequency save in memory
every 5s
Frequency command range 01-01(P.2)~01-00(P.1),
frequency command value from RH,RM setting
Remote setting function
In external mode, combined mode 1,combined mode 5, use digital input to change output frequency.
Acceleration
RH
Deceleration
RM
Clear
RL
Run forward
STF
ON
ON
ON
ON ON ON
ON
ON
ON
Power
Output
frequency
Hz
0
Time
*
When 10-11(P.61)=0X target frequency is set by exterior signal(except multi-speed) or set
in PU mode, name as main target frequency.
When 10-11(P.61)=1X it is 01-01: minimum frequency.
10-11(P.61)=X1/X2/X4
10-11(P.61)=X3
10-11(P.61)=X2/X3
10-11(P.61)=X1/X4
Remote function setting
1. 10-11(P.61) decides remote function and ways to save frequency.
Set 10-11(P.61)=X1~X4(remote control function on), terminal RM, RH, RL will be accelerate (RH),
decelerate (RM) and clear (RH).See following figure:
Inverter
Forward
Acceleration
Deceleration
Clear
STF
RH
RL
RM
SD