Protection parameter group 06
PARAMETER DESCRIPTION 118
5.When in fire mode, the inverter does not execute PID function. Any operating PID function is invalid automatically.
6.When in fire mode, the inverter does not execute the starting DC brake function. Any operating DC brake is invalid
automatically when in fire mode.
7.When in fire mode, the inverter does not execute over-current stall prevention function. Any operating over-current
stall prevention is automatically invalid when in fire mode.
8.When in fire mode, if low voltage, the inverter keeps running or stopped when no power.
9.When in fire mode, the output stop function (MRS,P_MRS) is invalid.
10. When in fire mode, the operating frequency for 06-85(P.208) cannot be larger than 01-00(P.1).if 06-85(P.208)
larger than 01-00(P.1), the maximum frequency is automatically set to 01-00(P.1)