After canceling secure communication, the safety function is stopped and the
de
vice reports an application error. Once the connection is established again, you
must send the Restart safety function command to the device via the PDO or Safety
Designer.
Aut
omatic start after connection
After aborting the safe communication, the safety laser scanner signals to W
ait for
inputs. As soon as the connection has been reestablished, the device automatically
switches to the current monitoring case. No additional command is required.
Restart behavior
You define whether the internal restart interlock of the network outputs is used.
Available network outputs
S
afety Designer displays which network outputs are available.
If you have not specified an input source, you can specify the network output here.
CONFIGURATION 7
8025220/1L9Q/2023-08-14 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherCA
117
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK EtherCAT microScan3 and is the answer not in the manual?

SICK EtherCAT microScan3 Specifications

General IconGeneral
Scanning angle275°
InterfacesEtherCAT
Protection classIP65
Supply voltage24 V DC
Resolution for protective field30 mm
Operating voltage24 V DC
Scanning range5.5 m
Number of fields128
Number of monitoring cases128
Response time30 ms
Operating temperature0 °C to 50 °C
Field of applicationIndustrial safety
Light sourceInfrared laser, 905 nm