S
tart safety function
Restart device completely
Reset
Data available (output of the device, input of the control):
Application error
Contamination error
Contamination warning
Current monitoring case
Device error
Manipulation
Cut-off path (Not safety-related)
Reference contour monitoring
Reset required
Status of safety function
Cut-off path (safety-oriented)
Status sleep mode
Complementary information
Inf
ormation on using the non-safety-related PROFINET EtherCAT PDO (0x1B00):
EtherCAT-PDO 0x1B00 contains the same information as the FSoE PDO 0x1A01
(18byte).
EtherCAT PDO 0x1B00 must not be used for safety-related tasks.
Further topics
"In
puts and outputs", page 116
"Process data in detail", page 172
4.6 Testing plan
The protective device must be tested by appropriately qualified safety personnel when
commis
sioning, after modifications and at regular intervals.
The manufacturer and user must define the type and frequency of the thorough checks
of the machine on the basis of the application conditions and the risk assessment.
Determination of the thorough checks must be documented in a traceable manner.
The following tests must be planned:
Before commissioning the machine and after making changes, you must check
whether the safety functions are fulfilling their planned purpose and whether
persons are being adequately protected.
The regular tests of the safety laser scanner must fulfill certain minimum require‐
ments.
A test object is required for some thorough checks. An optically opaque cylinder with
a black surface can be used as a suitable test object. The diameter must match the
configured resolution.
4.6.1 Planning the thorough check during commissioning and in certain situations
Minimum requirements
T
he protective device and its application must be thoroughly checked in the following
situations:
Before commissioning
After changes to the configuration or the safety function
After changes to the mounting, the alignment or the electrical connection
After exceptional events, such as after manipulation has been detected, after
modification of the machine, or after replacing components
PROJECT PLANNING 4
8025220/1L9Q/2023-08-14 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherCA
69
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK EtherCAT microScan3 and is the answer not in the manual?

SICK EtherCAT microScan3 Specifications

General IconGeneral
Scanning angle275°
InterfacesEtherCAT
Protection classIP65
Supply voltage24 V DC
Resolution for protective field30 mm
Operating voltage24 V DC
Scanning range5.5 m
Number of fields128
Number of monitoring cases128
Response time30 ms
Operating temperature0 °C to 50 °C
Field of applicationIndustrial safety
Light sourceInfrared laser, 905 nm
Connection typeM12
Weight1.2 kg