Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
203
Relay dead band (2.8.2.5.)
Sets the distance above and below the bound alarm setpoints.
Index Relay
Values Range: 0.000 ... Span( 2.2.2.) (Page 169) value, or equivalent, depending on
Units (2.1.1.) (Page 162).
Preset: 2% of Span (2.2.2.) (Page 169).
Related
• Relay function (2.8.1.4.) (Page 195)
• ON setpoint (2.8.1.5.) (Page 197)
• OFF setpoint (2.8.1.6.) (Page 197)
Note
This parameter applies only to in
-bounds and out-of bounds relay functions.
For In-bounds and Out-of-bounds Relay Functions [Relay Function (2.8.1.4.) (Page 195) =
In-bounds and Out-of-bounds, respectively], a dead band prevents relay chatter due to
material level fluctuations at both the upper and lower setpoints.
Enter the dead band in units of measure [
Units (2.1.1.)
162)]. The dead band value is applied both above
and below the upper and lower bound setpoints as
shown in the figure.
Actual On or OFF setpoint
and (2.8.2.5.)
ON setpoint (2.8.1.5.) (Page 197) or OFF setpoint (2.8.1.6.) (Page 197)
Actual OFF or ON setpoint