Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
213
Mantissa (2.10.2.2.)
Establishes the number of flow units required to increment the Flow Sampler (the device
connected to the relay set to Relay Function (2.8.1.4.) (Page 195) = Flow Sampler), in
conjunction with Exponent (2.10.2.3.) (Page 214).
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0.001 ... 9999
Preset: 1.000
Related
Sensor mode (2.1.3.) (Page 163)
Relay function (2.8.1.4.) (Page 195)
Primary measuring device (2.13.2.) (Page 240)
Flow exponent (2.13.4.1) (Page 241)
PMD dimensions (2.13.5.) (Page 246)
Maximum head (2.13.4.2.) (Page 243)
Maximum flow (2.13.4.3.) (Page 243)
Zero head (2.13.4.5.) (Page 244)
Flow time units (2.13.4.4.) (Page 244)
Flowrate decimal (2.13.4.6.) (Page 245)
Head 1 (2.13.6.1.1.) (Page 247)
Flow 1 (2.13.6.1.2.) (Page 248)
Low flow cutoff (2.13.4.8.) (Page 246)
Auto zero head (2.13.3.) (Page 240)
Exponent (2.10.2.3.) (Page 214)
This parameter is relevant only if Operation is set to OCM [Sensor Mode (2.1.3.) (Page 163)
= Flow rate in open channel].
Enter the mantissa (Y) for the exponent (Z) in the formula:
Flow Sampler Increment = Y x 10
Z
Flow units
Example: To count once every 4310 (4.31 x 10
3
) flow units: set Mantissa (2.10.2.2.) to 4.31
and Exponent (2.10.2.3.) (Page 214) to 3.