Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
244 Operating Instructions, 06/2018, A5E36281317-AC
Example
Conditions
Enter
Flowrate display: millions of gallons/ day, and
maximum flowrate is 376,500,000 gallons/day.
376.5 for Maximum Flow (2.13.4.3.), and Days for
Flow Time Units (2.13.4.4.) (Page 244)
Flow time units (2.13.4.4.)
Defines the units used to display current flow and logging flow values.
Index
Single-point model
Dual-point model
Global
Transducer
Options
Seconds
Minutes
Hours
*Days
Altered by
Flowrate units (2.13.4.7.) (Page 245)
This is used when the Primary Measuring Device is Ratiometric [Flowrate Units (2.13.4.7.)
(Page 245) = Ratiometric].
Example
Conditions
Enter
Flowrate display: millions of gallons/day, and
maximum flowrate is 376,500,000 gallons/day.
376.5 for Maximum Flow (2.13.4.3.) (Page 243),
and Days for Flow Time Units (2.13.4.4.)
Zero head (2.13.4.5.)
The distance above Empty (2.2.4.) (Page 170), in Units (2.1.1.) (Page 162) representing
zero head (and zero flow).
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: -999 ... 9999
Preset: 0.000
Altered by
Units (2.1.1.) (Page 162)
Span (2.2.2.) (Page 169)
Related
Empty (2.2.4.) (Page 170)
Range extension (2.2.7.) (Page 172)
Head (3.2.8.13) (Page 258)
This feature can be used for most weirs and some flumes (e.g. Palmer-Bowlus) where the
zero reference is at a higher elevation than the channel bottom.