Electrical connection
5.6 Additional system components
SINAMICS DCP
104 Operating Instructions, 09/2019, A5E34382853K
5.6.4.10 Technical data
Table 5- 33 Technical data
6SL3055-0AA00-3AA1
Unit
Value
Electronic power supply
Voltage
Current (without DRIVE-CLiQ or
digital outputs)
Power loss
V
DC
A
DC
W
24 DC (20.4 – 28.8)
0.5
<10
PE/ground connection
On enclosure with M4/1.8 Nm screw
Response time The response time for the digital inputs/outputs and the analog
inputs/outputs consists of the following elements:
• Response time on the component itself (approx. 1/2 DRIVE-
CLiQ clock cycle).
• Transmission time via the DRIVE-CLiQ connection (approx. 1
DRIVE-CLiQ clock cycle)
• Evaluation on the Control Unit (see function diagram)
Further information: SINAMICS DCP List Manual, Chapter "Func-
tion diagrams".
PE/ground connection
At the housing with M4 screw
Maximum cable lengths:
Electronics power supply
DRIVE-CLiQ cables
inputs/outputs
m
m
m
30
100
30
Ventilation clearances,
above/below
mm 50
Weight
kg
0.49