Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
105
5.6.5 Terminal Module TM150
5.6.5.1 Description
The terminal module TM150 is a DRIVE-CLiQ component for temperature evaluation. The
temperature is measured in a temperature range from -99 °C to +250 °C for the following
temperature sensors:
● PT100 (with monitoring for wire breakage and short-circuit)
● PT1000 (with monitoring for wire breakage and short-circuit)
● KTY84 (with monitoring for wire breakage and short-circuit)
● PTC (with short-circuit monitoring)
● Bimetallic NC contact (without monitoring)
For the temperature sensor inputs, for each terminal block the evaluation can be
parameterized for 1x2-wire, 2x2-wire, 3-wire or 4-wire conductors. There is no galvanic
isolation in the TM150.
The TM150 is mounted in the control cabinet and can be snapped on to a standard mounting
rail (EN 60715).
The TM150 contains the following interfaces:
Table 5- 34 Overview of the TM150 interfaces
Temperature sensor inputs 12
5.6.5.2 Safety instructions
Non-observance of the safety instructions
If the safety instructions in Chapter 1 are not observed, accidents can occur involving
severe injuries or death.
• Make sure that the safety instructions are observed.