Technical specifications
10.2 Device data
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
427
10.2 Device data
Table 10- 2 Technical specifications of the 30 kW device
Rated DC voltage V 600
Rated DC current A 50
Operating voltage range V 0 ... 1000 Applicable for side 1 and side 2
Overvoltage range V 800 ... 1000 Applies for side 1 and side 2:
after switching on and off, voltages are only permissi-
ble in this range for 30 s.
Operation is possible with a reduced current (5 A at
DC system voltage V 1000 According to IEC 62109-1 (PV and battery circuits)
AC system voltage V 600 According to IEC 61800-5-1
Recurring peak voltage V 940 between the DC line connections (P1, N1, P2, N2) and
housing / ground (according to EN 60664-1:2007)
In the voltage range 0 V … 600 V
In the voltage range 600 V … 800 V
Inductance of the energy storage
µH 700 per power unit
Monitoring The device shuts down by means of hardware moni-
toring for voltages greater than 1000 V and for cur-
rents greater than 60 A.
The device can generate a maximum short-circuit
DC electronics power supply V 24 Permissible voltage range: 18 … 30 V
Current consumption: 5 A at 24 V
Degree of protection IP20 The following applies to applications in Australia:
The enclosure of the device does not meet the re-
quirements of a fire enclosure. Therefore, the device
must be installed in a suitable enclosure to meet the
application and site requirements.
Use Exclusively for cabinet installation
Forced air cooling with integrated fans
3