EasyManua.ls Logo

Siemens sinamics dcp - 7.4.4 Parallel operation of communication interfaces

Siemens sinamics dcp
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
7.4 Communication according to PROFIdrive
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
193
7.4.4 Parallel operation of communication interfaces
Cyclic process data (setpoints / actual values) are processed using interfaces IF1 and IF2.
The following interfaces are used:
Onboard interfaces of the CUD for PROFIBUS DP
An additional interface (COMM-BOARD) for PROFINET or SINAMICS Link, EtherNet/IP
and MODBUS (CBE20) for insertion in the CUD as option
Parameter p8839 is used to set the parallel use of the onboard interfaces of the CUD and of
the COMM-BOARD in the SINAMICS system. The functionality is assigned to interfaces IF1
and IF2 using indices.
For example, the following applications are possible:
PROFIBUS DP for control and PROFINET to acquire actual values / measured values of
the drive
PROFIBUS DP for control and PROFINET for engineering only
Mixed mode with two masters (the first for logic and coordination, and the second for
technology)
SINAMICS Link via IF1 (CBE20); PROFIBUS on IF2
Operation of redundant communication interfaces
Assignment of communication interfaces to cyclic interfaces
The two cyclic interfaces for the setpoints and actual values differ by the parameter ranges
used (BICO technology, etc.) and the functions that can be used. The interfaces are
designated as cyclic interface 1 (IF1) and cyclic interface 2 (IF2).
With the factory setting p8839 = 99, the communication interfaces are permanently assigned
one of the cyclic interfaces (IF1, IF2), depending on the communication system, e.g.
PROFIBUS DP, PROFINET.
The assignment to the cyclic interfaces can essentially be freely defined by user
parameterization for the parallel operation of the communication interfaces.