Operation
7.7 Communication via Modbus TCP
SINAMICS DCP
280 Operating Instructions, 09/2019, A5E34382853K
Table 7- 34 Assignment of the Modbus register for general parameter access using DS47
Register
Description
Ac-
cess
Unit
Scaling
ON/OFF text
or Value range
Data / parameter
40601
DS47 Control
R/W
-
-
-
-
40602
DS47 header
R/W
-
-
-
-
40603
DS47 data 1
R/W
-
-
-
-
40722
DS47 data 120
R/W
-
-
-
-
Note
Limited value range
Modbus TCP registers have a maximum 16 bit width. The va
lues of display parameters (r
para
meters) cannot always be represented with 16 bits. In these particular cases, the
maximum value that can be represented is displayed.
Unsigned: 65535
Signed min: -32768
Signed max: 32767
7.7.4 Write and read access using function codes
Function codes used
For data exchange between the controller and device, predefined function codes are used
for communication via Modbus.
The Control Unit uses the following Modbus function codes:
FC 03: Holding register to read data from the inverter
FC 06: Write single register to write to individual register
FC 16: Write to multiple registers to write to several registers
Structure of a Modbus TCP message
Figure 7-47 Individual components, including the Modbus Application Header (MBAP) and function
code