Servicing
8.2 Replacing the fans
SINAMICS DCP
420 Operating Instructions, 09/2019, A5E34382853K
8.2.2 Replacing the fans for the 120 kW device
Figure 8-2 Replacing the fan of a 120 kW device
1. Release the 2 screws at the lower side of the device and remove the front panel
2. Withdraw connector
â‘
3. Loosen the screw
â‘¡
4. Replace the fan unit
5. Tighten the screw
â‘¡
6. Plug the connector
â‘ in
7. Re-attach the front panel and tighten the 2 screws at the lower side of the device