Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
111
Note
Incorrect temperature measured values as a result of cables with an excessively high
resistance
An excessively long cable length or an excessively small cable cross
-section can falsify the
mperature measurement (for a PT100, 10 Ω cable resistance can falsify the measurement
result by 10%). As a consequence, excessively high measured values are output, which
could lead to the motor being unnecessarily tripped prematurely.
Use only cable lengths ≤ 300 m.
For cable lengths >100 m, use cables with a cross-section of ≥1 mm
2
.
5.6.5.4 Connection examples
Figure 5-35 Connecting a PT100/PT1000 with 2x2, 3 and 4-wires to the temperature sensor inputs
X53x of Terminal Module TM150