SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
29
The SINAMICS DCP is only designed for cabinet mounting.
Note
Protection against the spread of fire
The device may be operated only in closed housings or in h
igher-level control cabinets with
protective covers that are closed, and when all of the protective devices are used.
The device must be installed in a metal co
ntrol cabinet or protected by another equivalent
measure such that fire cannot spread and emissi
ons outside of the control cabinet are
Note
Protection against condensation and electrically conductive dirt and pollution
To ensure that the device functions correctly, appropriately protect it for example by installing
it in a control cabi
net with degree of protection IP54 according to standard EN 60529 or
12 according to NEMA 250. Further measures may be necessary for particularly critical
A lower degree of cabinet protection is permissible, if condensation and c
onductive pollution
can be excluded at the installation site.
It must be mounted vertically.
The mandatory cooling clearances are indicated by the dotted line.
The arrangement of the fixing positions is shown in the following: