SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
425
10.1 Ambient conditions
Environmental classes according to EN 60721-3
Table 10- 1 Environmental classes
Operation Mechanical stability See
Remark
• Vibration test according to EN 61800-5-1 (Table 27)
– Test: Fc test according to IEC 60068-2-6
– Motion: Sinusoidal
– 10 to 57 Hz: Amplitude = 0.075 mm
– 57 to 150 Hz: Acceleration = 1 g
– Duration of vibration: 10 cycles per axis
Climatic influences 3K3
• in accordance with EN 60721-3-3
• Maximum surrounding air temperature: 0°C to +40°C (up
to + 55 °C with "Derating (Page 357)")
• No condensation, splash water or icing permitted.
Biological influences 3B1 -
Transporta-
tion
Mechanical stability 2M1
• Vibration test:
– 2 to 9 Hz: Amplitude = 3.5 mm
– 9 to 200 Hz: Acceleration = 10 m/s
2
Climatic influences 2K3
• in accordance with EN 60721-3-2
• Surrounding air temperature:
– -25° C to +70° C
(briefly to -40° C for max. 24 h)
Storage
Climatic influences 1K4
• in accordance with EN 60721-3-1
• Surrounding air temperature:
– -25° C to +55° C (temperature fluctuations ≤ 20 K / h)
Before commissioning, make sure that any condensation has