Operation
7.16 Diagnostics
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
369
Properties of the alarm buffer/alarm history:
The alarms in the alarm buffer are arranged from 7 to 0 according to the time that they
occurred. In the alarm history, this is from 8 to 63.
If eight alarms have been entered in the alarm buffer, and a new alarm is received, the
alarms that have been resolved are transferred to the alarm history.
r2121 is incremented each time the alarm buffer changes.
An alarm value (r2124) can be output for an alarm. The alarm value is used to diagnose
the alarm more accurately; please refer to the alarm description for details of the
meaning.
Clearing the alarm buffer, index [0...7]:
The alarm buffer index [0...7] is reset as follows: p2111 = 0.
7.16.3.3 Configuring messages
The properties of the faults and alarms in the SINAMICS DCP are permanently defined.
The following configuration settings can be made for some of the messages within a
permanently defined framework for the SINAMICS DCP:
Change message type (example)
Select message
Set message type
p2118[5] = 1057
p2119[5]
= 1: Fault (F)
= 2: Alarm (A)
= 3: No message (N)
Change fault reaction (example)
Select message
Set fault reaction
p2100[3] = 1910
p2101[3]
= 0: None
= 1: OFF1
= 2: OFF2
= 3: OFF3
Change acknowledgment (example)
Select message
Set acknowledgment
p2126[4] = 1800
p2127[4]
= 1: POWER ON
= 2: IMMEDIATE
= 3: PULSE INHIBIT