Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
113
5.6.5.5 Meaning of the LEDs on the Terminal Module TM150
Table 5- 39 Meaning of the LEDs at the Terminal Module TM150
READY
– Off Electronic power supply is missing or outside permissible
Check power supply
Green Continuous
light
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
–
Orange Continuous
DRIVE-CLiQ communication is being established. –
Red
Continuous
light
At least one fault is present in this component.
LED is controlled irrespective of the corresponding mes-
sages being reconfigured.
Remedy and
acknowledge fault
Green/
Red
Flashing
light
Firmware is being downloaded. –
Flashing
light
Firmware has been downloaded.
Wait for POWER ON.
Carry out a POWER
ON
Green/
orange
or
red/
Flashing
light
2 Hz
Component recognition via LED is activated (p0154).
Both options depend on the LED status when module
recognition is activated via p0154 = 1.
–
Cause and rectification of faults
The following documents contain information about the cause of faults and how they can be
rectified:
SINAMICS S120 Commissioning Manual with STARTER
SINAMICS DCP List Manual