Operation
7.7 Communication via Modbus TCP
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
277
7.7.2 Configuring Modbus TCP via interface X1400
Activating Modbus TCP via X1400 (CBE20)
1. For drive object CU_DCP, set p8835 = 5 (Modbus TCP).
2. Set the IP address for the CBE20 using p8941.
3. Set the standard gateway for the CBE20 using p8942.
4. Set the subnet mask for the CBE20 using p8943.
5. Set the DHCP mode for the CBE20 using p8944.
6. Select the setting "Activate and save configuration" as interface configuration using
p8945 = 2.
7. In the STARTER commissioning tool, check the list of drive object p0978.
If required, change the sequence of the drive objects using the telegram configuration
("Drive device" > "Communication" > "Telegram configuration").
8. Save the settings in the STARTER commissioning tool and carry out a POWER ON.
Modbus settings with interface X1400
Using the following parameters, set the communication for Modbus TCP with a X1400
interface:
r2050[0...19] Connector output to interconnect the PZD received from the fieldbus controller via
p2051[0...24] Selects the PZD (actual values) to be sent to the fieldbus controller in the word
r2053[0...24] Displays the PZD (actual values) sent to the fieldbus controller in the word format
Status display for the internal communication interface.
p8840 Setting the monitoring time to monitor the received process data via the COMM
BOARD.
If, within this time, the Control Unit does not receive any process data from the
COMM BOARD, then the drive shuts down with fault F08501.
p8839[0...1] Assigning the CBE20 Communication Board Ethernet (X1400) for cyclic communi-
cation via PZD interface 1 (IF1) and interface 2 (IF2).
r8850[0...19] Connector output to interconnect the PZD (setpoints) received in the word format
Selects the PZD (actual values) to be sent in the word format via IF2.
Displays the PZD (actual values) sent in the word format via IF2.
Status display for COMM BOARD.