Electrical connection
5.6 Additional system components
SINAMICS DCP
108 Operating Instructions, 09/2019, A5E34382853K
Terminal type
X524
Terminal type
Screw terminal
Connectable conductor
cross-section
Rigid, flexible
With wire-end ferrule without plastic sleeve
With wire-end ferrule with plastic sleeve
AWG / kcmil
0.2 ... 2.5 mm
2
0.2 ... 2.5 mm
2
0.5 ... 1.5 mm
2
22 ... 12
Stripped length
6 ... 7 mm
Tool
0.5 × 3 mm screwdriver
Tightening torque
0.4 to 0.5 Nm
X531 - X536
Terminal type
Spring-loaded terminal
Connectable conductor
cross-section
Rigid
Flexible
Flexible with wire-end sleeve without plastic sleeve
Flexible with wire-end ferrule with plastic sleeve
AWG / kcmil
0.2 ... 1.5 mm
2
0.2 ... 1.5 mm
2
0.25 ... 1.5 mm
2
0.25 ... 0.75 mm
2
24 … 16
Stripped length
10 mm
X500 and X501 DRIVE-CLiQ interfaces
Table 5- 35 X500/X501: DRIVE-CLiQ interfaces
Connector
Pin
Signal name
Technical specifications
1
TXP
Transmit data +
2
TXN
Transmit data -
3
RXP
Receive data +
4
Reserved, do not use
5
Reserved, do not use
6 RXN Receive data -
7
Reserved, do not use
8 Reserved, do not use
A
+ (24 V)
Power supply, max. 450 mA
B
M (0 V)
Electronics ground
Connector
type
DRIVE-CLiQ socket
The blanking co
vers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 units), article number: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE
-CLiQ cable length is 100 m.

Table of Contents