Operation
7.1 Operation
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
155
Reset parameters
The parameters can be reset to the factory setting as follows:
Start restoring all parameters to their factory settings
After this has been done, p0976 is automatically set to 0 and p0009 is set to 1.
Deleting all user data
In addition to the actual parameter data set which saves the parameter assignment of the
unit in a non-volatile memory (ROM) of the device and which can be deleted using p0976 = 1
(restore factory settings), the following data also belongs to the non-volatile user data:
● DCC charts
● The DCC block library
● Additional parameter data sets (see p0802, p0803, p0804)
Note
DCC is not supported in firmware version V1.1.
This data is also saved in the non-volatile memory (ROM). All user data is deleted from the
ROM as follows:
Start to delete all user data
The operation may take several minutes. The unit automatically powers up during this time.
As a result, the unit in STARTER goes offline. Re-connect with the drive. After this has been
done, p0976 is automatically set to 0 and p0009 is set to 0.
ta on the memory card is not deleted by setting p0976 = 200. In spite of this, when
deleting all user data, it is not permissible
that a memory card is inserted. An inserted
memory card would mean that for an automatic run
-up after p0976 = 200, as usual, the data
would be read from the memory card (see also Chapter "
Memory card functions
158)"). The device would ramp-up with the parameter assignment from the memory