Operation
7.1 Operation
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
155
Reset parameters
The parameters can be reset to the factory setting as follows:
p0009 = 30
Parameter reset
p0976 = 1
Start restoring all parameters to their factory settings
After this has been done, p0976 is automatically set to 0 and p0009 is set to 1.
Deleting all user data
In addition to the actual parameter data set which saves the parameter assignment of the
unit in a non-volatile memory (ROM) of the device and which can be deleted using p0976 = 1
(restore factory settings), the following data also belongs to the non-volatile user data:
DCC charts
The DCC block library
Additional parameter data sets (see p0802, p0803, p0804)
Note
DCC is not supported in firmware version V1.1.
This data is also saved in the non-volatile memory (ROM). All user data is deleted from the
ROM as follows:
p0009 = 30
Parameter reset
p0976 = 200
Start to delete all user data
The operation may take several minutes. The unit automatically powers up during this time.
As a result, the unit in STARTER goes offline. Re-connect with the drive. After this has been
done, p0976 is automatically set to 0 and p0009 is set to 0.
Note
Da
ta on the memory card is not deleted by setting p0976 = 200. In spite of this, when
deleting all user data, it is not permissible
that a memory card is inserted. An inserted
memory card would mean that for an automatic run
-up after p0976 = 200, as usual, the data
would be read from the memory card (see also Chapter "
Memory card functions
(Page
158)"). The device would ramp-up with the parameter assignment from the memory
card.