Operation
7.4 Communication according to PROFIdrive
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
189
Scaling BICOs
The following definitions apply for transferring process data:
For word interconnection (via p02051[..] or r02050[..])
+199.99 %
=23767
= 7FFF hex
+100.00 %
=16384
= 0x4000 hex
0.00% = 0 = 0000 hex
-100.00%
=-16384
= C000 hex
-200.00% =-32768 = 8000 hex
For double word interconnection (via p02061[..] or r02060[..])
+199.99 %
= 7FFFFFFF hex
+100.00 %
= 40000000 hex
0.00%
= 00000000 hex
-100.00%
= C0000000 hex
-200.00%
= 80000000 hex
Comment:
For DCP, the double word interconnection hardly has any practical significance as the
data to be transferred do not have the accuracy that would justify the high resolution
(32 bit).
In the DCP, the described conversion is automatically carried out by the BICO
interconnection.
Example 1:
BICO connection p2051[1] = r55501 (see FP2470 and FP6850) means that at PZD
word 1 the voltage at side 1 is cyclically sent to the higher-level control system.
If r55501 has a value of 100.00 %, then the value +16384 is received in the higher-
level control system. If r55501 = 50.00 % then a value of +8192 is received.
Example 2:
BICO connection p55050 = r2050[1] (see FP2460 and FP6805) means that at PZD
word 1, the setpoint for the current control, which is received from the higher-level
control system, is cyclically received.
If the higher-level control system sends a value of +16384, then this is interpreted as a
setpoint of +100.00 %. In operation, this value can be seen at r55070.
The following applies to the reference variables of the percentage values:
Voltages in the power unit, e.g. r55501, r55502:
Voltages are referred to the reference voltage (r50071). For a display or setting value
of 100.00 %, the voltage therefore corresponds to the reference voltage of SINAMICS
DCP. The rated voltage according to the technical data (Chapter "Device data
(Page 427)") is used as reference voltage.
Currents in the power unit, e.g. r55521, r55522, r55523:
Currents are referred to the reference current (r50072). For a display or setting value
of 100.00 %, the current therefore corresponds to the reference current of the
SINAMICS DCP. The rated current according to the technical data (Chapter "Device
data (Page 427)") is used as reference current.