Mounting
SINAMICS DCP
32 Operating Instructions, 09/2019, A5E34382853K
The area below the device must be unobstructed and allow sufficient supply air.
The area above the device must allow the air outlet and the air outlet openings of the device
must be unobstructed.
120 kW devices can be lined up directly next to one another.
For the 30 kW devices, as a result of the protruding screw heads, a clearance of
approximately 5 mm is required on the right-hand side.
The customer must ensure that power cables are clamped nor further than 300 mm from
their termination.
Note
For cabinet designs with degree of protection greater than IP20, an additional fan is required
if the power rating is fully utilized. This fan must be designed for the "fan air
flow" (see
"
Device data (Page 427)") of the device in question.
Figure 4-3 120 kW device with mounted transport aid
The 120 kW device is delivered with 3 metal brackets, which are used as a transport aid
(shown in red in the diagram above). These have to be removed before mounting and
disposed of as scrap metal.